A printable generator maintenance checklist for diesel and gas standby sets. It covers the engine, the batteries and charger, and a test run with the transfer switch. Use it for weekly checks or monthly service visits, then print it or save a PDF.
These are common checks to start from. Your machine’s manual and the safety rules for your site come first, so add or change checks to match them.
Want this check to come up on schedule? See how preventive maintenance plans work in Catalyces.
For emergency and standby generators in the US, the key standard is NFPA 110, Standard for Emergency and Standby Power Systems. Fire codes and inspectors use it, and hospitals reach it through NFPA 99. Your authority having jurisdiction decides which edition applies.
NFPA 110 calls for a weekly inspection of the generator set, including the batteries. It also calls for a monthly exercise of at least 30 minutes under load. The load must be at least 30% of the nameplate kW rating, or enough to reach the minimum exhaust temperature the manufacturer recommends.
Many buildings cannot put that much load on the set. In that case, NFPA 110 calls for a yearly load bank test. Long runs at light load are what cause wet stacking in diesel engines: unburned fuel and soot build up in the exhaust. A load bank burns it off and proves the set can carry the building.
Diesel fuel also ages in the tank. NFPA 110 calls for a fuel quality test at least once a year. Water and microbial growth in old fuel block filters at the worst moment, during a real outage.
Keep every test on record: the date, running hours, load, voltage, frequency and who ran it. Inspectors and insurers ask for that log first.